Magpowr DIGITRAC 2 Instruction Manual - page 15
8.
RESET PROCEDURES
If it is desired to reset parameters to factory default values perform one of the following reset procedures:
A.
1.
Simultaneously press
é and ê and hold for 2 seconds. )RESETTING PARAMETERS( will
appear on the screen for 1 second.
2.
Program reset is complete. The basic (tension sensor) calibration is still in memory, but
dynamic calibration must be reprogrammed.
or
B.
1.
Connect TB4.6 to TB4.3 for 2 seconds.
2.
When
)REMOVE FORMAT SIGNAL TO START( appears, remove connection.
3.
Program reset is complete. The basic (tension sensor) calibration is still in memory, but
dynamic calibration must be reprogrammed.
or
C.
1.
Turn the power to the DIGITRAC 2
)OFF( for 5 seconds.
2.
Press SHIFT and 3 simultaneously.
3.
While holding the keys down, turn the power
)ON(.
4.
Release both keys when the screen appears. The screen will display
)TEST OR NORMAL?
TEST
(
5.
Press ENTER to display
)DISABLE WATCHDOG
NO
(
6.
Press PRIOR ITEM to display
)TEST OR NORMAL?
TEST
(
7.
Press
é to display )TEST OR NORMAL?
NORMAL
(
8.
Press ENTER.
9.
Program reset is complete. The basic (tension sensor) calibration has been erased, and all
other programming has been reset to factory default values. Begin at Section 4 to reprogram.
15